Northern Telecom IBDN User Manual contains an Appendix D titled
"UTP Separation Guidelines From EMI Sources". The values are the
same as the cabling pathways standard, EIA-569, table 4.8-5.
Minimum Separation Distance from Power Source at 480V or less CONDITION <2kVA 2-5kVA >5kVA Unshielded power lines or electrical equipment in proximity to open or non-metal pathways 5 in. 12 in. 24 in. (12.7 cm) (30.5 cm) (61 cm) Unshielded power lines or electrical equipment in proximity to grounded metal conduit pathway 2.5 in. 6 in. 12 in. (6.4 cm) (15.2 cm) (30.5 cm) Power lines enclosed in a grounded metal conduit (or equivalent shielding) in proximity to grounded metal conduit pathway - 6 in. 12 in. - (15.2 cm) (30.5 cm) Transformers & electric motors <------- 40-in (1.02 m) -----> Fluorescent lighting <------- 12-in (30.5 cm) ---->
 